Class I Division II means the project site may produce combustible gas, vapor abnormally when the project operates, here are some recommended explosion proof lighting, control box and fittings for your options subject to NEC UL and CSA standard.
In Simple Word
Class 1 Div 2 location, C1D2 for short, Class 1 Division 2 for full name, means ignitable concentrations of hazards, such as flammable vapors and gases, exists under abnormal operation conditions.
In Quantitative Measurement
Class 1 Div 2 location means ignitable concentrations of hazards, such as flammable vapors and gases, present from 1 hour to 10 hours every year.
A Class 1, Division 2 location is a location:
In which volatile flammable gases, flammable liquid-produced vapors, or combustible liquid-produced vapors are handled, processed, or used, but in which the liquids, vapors, or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems or in case of abnormal operation of equipment, or
In which ignitible concentrations of flammable gases, flammable liquid-produced vapors, or combustible liquid-produced vapors are normally prevented by positive mechanical ventilation and which might become hazardous through failure or abnormal operation of the ventilating equipment, or
That is adjacent to a Class 1, Division 1 location, and to which ignitible concentrations of flammable gases, flammable liquid-produced vapors, or combustible liquid-produced vapors above their flash points might occasionally be communicated unless such communication is prevented by adequate positive-pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided.
C1D2
UL/Intertek
Nema4X
Class I Division 1
Zone 1&2, Zone 21&22
LED 30-240W
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
LED 30-150W
Type 4X, IP66
Class I Division 2
Zone 2, Zone 21&22
LED 30-300W
Type 4X, IP66
Class I Division 2
Zone 2, Zone 21&22
LED30-240W
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
LED 20-200W
Type 4X, IP66
Class I Division 2
Zone 2, Zone 21&22
LED 20-400W
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
LED 80-300W
Type 4X, IP66
Class I Division 2
Zone 2, Zone 21&22
LED 40-150W
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
LED 20-120W
Type 4X, IP66
Class I Division 2
Zone 2, Zone 21&22
LED 20-80W
Type 4X, IP66
Class I Division 2
Zone 1&2, Zone 21&22
LED 9-80W
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
LED 2x5W
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
LED 5W
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
LED 5W
Type 4X, IP66
Class I Division 1
Zone 1&2, Zone 21&22
LED 2x5W
Type 4X, IP67
Class I Division 1
Zone 1&2, Zone 21&22
LED 5W
Type 4X, IP65
Class I Division 1
Zone 1&2, Zone 21&22
LED 5W
Type 4X, IP68
Class I Division 1
Zone 1&2, Zone 21&22
LED 2x5W
Type 4X, IP65
Class I Division 1
Zone 1&2, Zone 21&22
LED 5W
Type 4X, IP65
Class I Division 1
Zone 1&2, Zone 21&22
LED 5W
Type 4X, IP67
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.32A
Type 4X, IP66
Built-in Switch
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.32A
Type 4X, IP66
Built-in Switch
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.32A
Type 4X, IP66
Built-in Terminal blocks
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.32A
Type 4X, IP66
Built-in Terminal blocks
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.125A
Type 4X, IP66
Built-in Terminal blocks
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.400A
Type 4X, IP66
Built-in Terminal blocks
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.250A
Type 4X, IP66
Built-in Terminal blocks
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.125A
Type 4X, IP66
Built-in Terminal blocks
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.125A
Type 4X, IP66
Built-in Terminal blocks
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.630A
Type 4X, IP66
Built-in Terminal blocks
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.250A
Type 4X, IP66
Built-in Terminal blocks
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.630A
Type 4X, IP66
Built-in Terminal blocks
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.200A
Type 4X, IP66
Built-in Terminal blocks
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.160A
Type 4X, IP66
Built-in Terminal blocks
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.160A
Type 4X, IP66
Built-in Terminal blocks
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.250A
Type 4X, IP66
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.1200A
Type 4X, IP66
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.630A
Type 4X, IP66
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.250A
Type 4X, IP66
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.250A
Type 4X, IP66
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
<125A
Type 4X, IP66
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
<125A
Type 4X, IP66
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.M63x1.5
Type 4X, IP65
Plastic
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.M75x1.5(NPT 2 1/2")
Type 4X, IP66
Mental
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.M75x1.5(NPT 2 1/2")
Type 4X, IP66
Non-armored
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.M75x1.5(NPT 2 1/2")
Type 4X, IP66
Armored
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.115x1.5(NPT 4")
Type 4X, IP66
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.115x1.5(NPT 4")
Type 4X, IP66
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.115x1.5(NPT 4")
Type 4X, IP66
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.115x1.5(NPT 4")
Type 4X, IP66
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.115x1.5(NPT 4")
Type 4X, IP66
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.115x1.5(NPT 4")
Type 4X, IP66
C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.63x1.5(NPT 2")
Type 4X, IP66
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.63x1.5(NPT 2")
Type 4X, IP66
C1D1, C1D2, C2D1, C2D2
Zone 1&2, Zone 21&22
Max.63x1.5(NPT 2")
Type 4X, IP66
Yes, Class 1 Div 2 require explosion proof. According to Class 1 Div 2 requirements, considering the existing frequency of ignitable gas of Class 1 Div 2 is not higher than Class 1 Div 1, led lighting should at least be constructed properly as “explosion proof” to limit the energy or isolate the ignition sources physically to prevent future explosion from happening, let alone the spreading of explosion.
Class 1 Division 2 hazardous area produce flammable vapors or gases which are further divided into Class 1 Division 2 Groups A-D. Hazardous material come out in abnormal conditions, such as system or container failures, leaks or ruptures and do not expected to always exist, only under unusual conditions. C1D2 room should install electrical device abide by electrical rating class 1 division 2.
Yes, when you intend to use electrical enclosure or panel in hazardous location, it is crucial to keep any combustible substances such as gases, vapors from entering into the confined housing and influencing the working of the electrical components inside. NEMA 4 and NEMA 4X protection rating lay the rational foundation for anti-explosion performance of nema 4x class 1 division 2 explosion proof enclosure.
Class 1 Division 2 Enclosure is used in facilities that flammable gases, vapors, and liquid materials are unlikely to present. Different from Class 1 Div 1 enclosure, Class 1 Div 2 enclosure should be factory sealed with at least Nema 4X rated standard as “nema explosion proof”, housed by glass reinforced plastic, stainless steel or aluminum alloy material control the potential to bring about ignition source via restrain high heat, temperature of electrical parts.
Yes, no matter what kind of outlets from such as conduit system, cables, cable entries of light fixtures, boxes, receptacles, switches, when the environment meet the electrical rating class 1 division 2 or flammable gas or vapors spread through any space or gaps within the whole system, sealing off for any bonding surface is essential to reduce the risk for concentration of hazards subject to class 1 div 2 seal off requirement.